GEZE

GEZE MBZ 300

Modular smoke and heat extraction (SHEV) control panel

GEZE MBZ 300

Emergency power control unit for 24 V DC smoke and heat extraction drives. The modular design allows flexible adaptation to the project — extendable by alarm groups, ventilation groups and alarm lines. The heart of the SHEV installation, tying together drives, buttons and weather sensors.

Technical Specifications

Total current consumption10 A – 72 A (depending on configuration)
Supply voltage230 V AC
Output current (max.)72 A
HousingSheeting, grey RAL 7035
IP ratingIP30
Temperature range-5 … +40 °C
Motor cable wire sizeup to 10 mm²
NetworkingSeveral control units via optional CAN Bus modules
Status contacts1 status contact per CM/SM, 6 signal contacts per ERM
Parameter settingUSB interface and PC software
Tested in accordance withEN 12101-10
ApprovalsVdS

Key Features

Variants

ModelType
MBZ 300 N8Control panel, 8 A version
MBZ 300 N10Control panel, 10 A version
MBZ 300 N24Control panel, 24 A version
MBZ 300 N48KControl panel, 48 A version (compact)
MBZ 300 N48GControl panel, 48 A version (large housing)
MBZ 300 N72Control panel, 72 A version

Portfolio and catalog data

Full listing of the control panels and the complete peripheral portfolio. Each item links to the manufacturer's catalog / technical data.

Control panel (SHEV)

MBZ 300 (N8 / N10 / N24 / N48K / N48G / N72)
Modular emergency power control unit, 10–72 A, EN 12101-10, VdS certified

Window drives (IQ windowdrive)

Slimchain
Slim-design chain drive for façades; strokes 300 / 500 / 800 mm, EN 12101-2 (SHEV)
Powerchain
Chain drive for large and heavy windows needing large opening widths; strokes 600 / 800 / 1200 mm
RWA 100 NT (with E 250 NT)
Opening and locking system for inward-opening windows, with E 250 NT spindle drive

Locking drive

Power lock
Locking drive in combination with Slimchain, Powerchain or E 250 NT; up to 6 locking points, locking/unlocking in 6 seconds

Safety

IQ box Safety
Module protecting the closing edges (pinch protection) via safety edges and non-contact sensors; TÜV tested per DIN EN 13849-1

Control panel accessories

FT 4 A / FT4 K
SHEV buttons for manual activation
LTA-24-AZ / LTA-LSA
Vent switches / buttons
GC 401 RS / GC 402 WVS / GC 403 WDS
Rain sensor, wind speed sensor and wind direction sensor
RM 1003 / WM 1005
Optical smoke detector and heat detector for automatic activation

Planning and regulatory framework

RWAtoday
Fundamentals, planning aids, regulations and guidelines for smoke control and natural ventilation
RWAupdate 4 / 5
Natural smoke ventilation through façades and roofs (4); stairwell smoke ventilation (5)

Applications

stairwells atriums shopping centres industrial halls underground car parks office buildings