The FC121-ZA is a conventional fire control panel with an integrated operating unit for 2 zones. The control unit has been designed to be very simple to use while offering exceptional flexibility via a comprehensive feature list. The FC121-ZA is ideally suited for small applications, e.g. in schools, shops, hotels. Expansions and accessories must be ordered separately.
Attribute | Value |
Operating voltage | DC 21…28.6 V |
Mains voltage | AC 196...253 V |
Power supply | 25 W |
Operating current | Max. 0.9 A |
Emergency power supply | Up to 72 Ah |
Battery capacity | 2x 12 V / 4 or 7 Ah |
Relay outputs | 1x dialer fault |
Operating temperature | -5…+40 °C |
Monitored output | 1x sounder line , 1x dialer fire |
Programmable inputs | 2 |
Plug-in position | 1 |
Zones | 2 |
Conventional devices per zone | Max. 32 |
Relative humidity | ≤95 % rel. (no condensation) |
Storage temperature | -20…+60 °C |
Protection category | IP30 |
Color housing/cover | ~RAL 000 50 00, Gray |
Dimensions (W x H x D) | 310 x 360 x 85 mm |
Accessories | FCA1206-Z1 Key switch set (Nordic SE) , FCA1209-Z1 Output module (230 V) , FDCH221 Housing for input/output modules , AX1213 Battery (12 V, 4.5 Ah) , FA2003-A1 Battery (12 V, 7 Ah, VDS) |
Expansion | FCA1203-Z1 Output card 2M 2R , FTO1201-H1 EVAC module (NL 2&4 zones) |