Combined fire detection and extinguishing control panel

A compact panel for installations with a single extinguishing zone. Manages detection, evaluation, alarming, and extinguishing activation in one device, with a built-in extinguishing function card.
| Detector line | 1 loop (max. 126 addresses) or 2 branches (max. 32 addresses/branch) |
| Compatible peripherals | XC361-ZA: Cerberus FIT/PRO (C-NET); XC3610-AA/-FA: Sinteso (FDnet) |
| Extinguishing zones | 1 (replaces the XC10 panel) |
| Extinguishing I/O card (XCI3601-A1) | 5 monitored outputs (actuator/alarm/reverse/pyro), 3 monitored inputs, 2 monitored collective inputs (up to 8 devices each) |
| Sounder lines | 2, each max. 0.5 A @ DC 24 V, monitored for open/short circuit |
| Relay outputs | 3, freely configurable (Fire control / RT Fire / RT Fault / Fire alarm), 2 A @ DC 60 V |
| Inputs/outputs | 4 freely configurable, DC 24 V / 0.1 A |
| Power supply | AC 230 V +10/-15 %, 50…60 Hz, 80 W, fuse AC 250 V/2.5 AT |
| Batteries | 2× 12 V / 25 Ah, sealed lead-acid (BAT12-25, S54302-Z102-A1), in series for 24 V |
| Emergency power | up to 72 hours |
| Dimensions (W×H×D) | 402 × 372 × 211 mm, 7.18 kg (without batteries) |
| Housing color | ~RAL 9003, Signal White |
| Operating/storage temperature | -5…+40 °C / -20…+60 °C, ≤95% RH (non-condensing) |
| Protection class | IP30 |
| Configuration | Built-in web-based 'XC360 Panel Configurator' over Ethernet, or PC software; auto-configuration for simple systems |
| Event memory | max. 2000 events, alarm counter max. 999 |
| Model | Peripherals | Addresses | Stock No. | Note |
|---|---|---|---|---|
| XC361-ZA | Cerberus FIT / Cerberus PRO (C-NET) | 126 | S54395-C1-A1 | Full support for EN 54-2 options 7.8, 7.9.1, 7.9.2, 7.11 |
| XC3610-AA | Sinteso (FDnet) | 126 | S54395-C1-A2 | Full support for EN 54-2 options 7.8, 7.9.1, 7.9.2, 7.11 |
| XC3610-FA | Sinteso (FDnet), France variant | 126 | Without EN 54-2 options 7.8, 7.9.1, 7.9.2, 7.11 |