Safety module for protecting hazardous areas of power-operated windows

IQ box Safety ensures that automated ventilation windows close safely by protecting the main and secondary closing edges. If the sensors detect a foreign object, the window is stopped or the closing motion is reversed. Especially necessary in nursery and primary schools, where children are considered in need of special protection.
| Dimensions | 35 × 90 × 60 mm |
| Type of installation | Top hat rail (35 mm) in a control cabinet or suitable housing |
| Operating voltage | 24 V DC |
| Current consumption | 0.1 A |
| Cable dimensions (max.) | 2.5 mm² |
| Max. total length to drives | 50 m |
| Max. cable length, non-contact sensors | 10 m |
| Max. cable length, safety edges | 200 m |
| Inputs for sensors | 4 |
| Scope | One module per window — up to 4 window drives and 2 locking drives |
| Functional safety | TÜV tested in accordance with DIN EN 13849-1 |
| Protection rating (Machinery Directive) | Level 4 — most stringent demands in the risk assessment |