Electrochemical detectors for carbon monoxide and nitrogen dioxide in car parks

A range of addressable detectors with an electrochemical sensor, specially designed for car parks and small installations. Two gas models (CO and NO₂), each in a 3-wire (proprietary addressable protocol) or 4-wire RS485 version, compatible with the DURPARK and DURGAS control panels respectively.
| Technology | Microprocessor and electrochemical sensor |
| Supply voltage | 9–15 V DC |
| Consumption | 14 mA standby / 24 mA in alarm |
| Sensor life | >5 years (CO), 3 years (NO₂), virtually maintenance-free |
| Automatic calibration | Software zero/gain algorithm; CO sensor sensitivity check without applying gas |
| Operating temperature | -10…+60 °C, relative humidity 5–90% (non-condensing) |
| Protection class / material | IP20 / ABS housing |
| Communication | 3-wire, proprietary addressable protocol (1–16) or 4-wire RS485 (DURPARK RS485) |
| Model | Gas | Wiring | Range | Resolution | T90 Response | Coverage |
|---|---|---|---|---|---|---|
| DURPARK CO | CO | 3-wire | 0–300 ppm | ±1 ppm | <90 s | ~200 m² (per Spanish standard) |
| DURPARK CO RS485 | CO | 4-wire (RS485) | 0–300 ppm | ±1 ppm | <90 s | ~200 m² |
| DURPARK NO₂ | NO₂ | 3-wire | 0–20 ppm | ±0.5 ppm | <30 s | ~100 m² (recommended) |
| DURPARK NO₂ RS485 | NO₂ | 4-wire (RS485) | 0–20 ppm | ±0.5 ppm | <30 s | ~100 m² |